Beckett BK171UL

Beckett BK171UL Condensate Pump with Safety Switch User Manual

Model: BK171UL

1. Ynlieding

This manual provides detailed instructions for the installation, operation, and maintenance of the Beckett BK171UL Condensate Pump. This pump is designed for automatic removal of condensate from HVAC equipment, including air conditioners, furnaces, boilers, dehumidifiers, and high-efficiency oil or gas-fired furnaces. It is suitable for condensate water temperatures up to 150°F and acidic condensate.

Beckett BK171UL Condensate Pump

Image 1.1: Beckett BK171UL Condensate Pump, front view.

2. Safety Information

WARSKÔGING: Risiko op elektryske skok. Skeakelje de stroom út foardat jo ûnderhâld útfiere.

  • Lês alle ynstruksjes soarchfâldich foar ynstallaasje en operaasje.
  • Soargje derfoar dat de stroomfoarsjenning oerienkomt mei it folume fan 'e pomptage (115V).
  • Brûk de pomp net mei in beskeadige snoer of stekker.
  • Dompelje de pomp net yn wetter.
  • This pump is designed for indoor use only.
  • Hâld hannen frij fan bewegende ûnderdielen tidens operaasje.
  • Soargje foar juste grûn as per lokale elektryske koades.
  • The pump is equipped with a safety switch. Ensure it is correctly wired to prevent overflow.

3. Package Ynhâld

Kontrolearje oft alle ûnderdielen oanwêzich binne foardat jo begjinne mei de ynstallaasje:

  • Beckett BK171UL Condensate Pump unit
  • 3/8" O.D. barbed check valve
  • Integrated 6-ft grounded power cord
  • Ynstruksjehânlieding (dit dokumint)
Exploded view of Beckett BK171UL Condensate Pump components

Ofbylding 3.1: Eksplodearre view showing pump components including cover, check valve, motor, fan, automatic switches, lift-to-test tab, bullseye level, floats, impeller, multi-slot metal mount tabs, 6 ft. grounded power cord, and collection tank.

4. Ynstallaasje en opset

4.1 Montage fan de pomp

The pump features stainless steel multi-slot mounting tabs for secure installation. Ensure the pump is placed on a level surface. Use the integrated bullseye level on the lid to confirm proper horizontal alignment.

Beckett BK171UL Condensate Pump installation features

Image 4.1: Close-up of pump showing bullseye level, twist lock check valve, and lift-to-test tab for easy installation and maintenance.

4.2 Condensate Inlet Connections

The pump is equipped with four 1-1/8-inch diameter inlet holes for connecting condensate drain lines from your HVAC equipment. Connect the drain line(s) to any available inlet(s).

4.3 Discharge Line Connection

Connect a 3/8" I.D. vinyl tubing (not included) to the 3/8" O.D. barbed check valve. The check valve twists to lock into place on the pump, preventing backflow of discharged water. Route the discharge line to an appropriate drain, ensuring it has a continuous downward slope and is free from kinks or obstructions. The pump can lift water up to 17 feet vertically.

4.4 Elektryske ferbining

Plug the 6-ft grounded power cord into a standard 115V electrical outlet. Ensure the outlet is properly grounded and protected by a ground fault circuit interrupter (GFCI) if required by local codes.

4.5 Safety Switch Wiring

The integrated safety switch is designed to shut down the HVAC equipment or trigger an alarm in case of a pump malfunction or high water level, preventing overflow. Consult your HVAC equipment manual for proper wiring of the safety switch. Typically, the safety switch wires are connected in series with the low-voltage thermostat circuit of the HVAC unit.

5. Operaasje

5.1 Automatic On/Off Operation

The Beckett BK171UL pump operates automatically. When condensate water in the collection tank reaches a predetermined level, the pump will activate, remove the water, and then shut off once the water level drops. This automatic cycle ensures efficient condensate removal without constant monitoring.

Beckett BK171UL Condensate Pump performance chart

Image 5.1: Diagram illustrating automatic ON/OFF operation and average performance at various lift heights (e.g., 95 GPH at 5 ft lift, 64 GPH at 10 ft lift, 17 ft shut-off).

5.2 Lift-to-Test Function

A "lift-to-test" tab is provided on the pump lid. Lifting this tab manually raises the float, simulating a high water level and activating the pump. This feature allows for quick testing of the pump's functionality and can also be used to drain the tank for servicing.

6. Underhâld

Regular maintenance ensures optimal performance and extends the life of your condensate pump.

  • Moanlikse ynspeksje: Visually inspect the pump, inlet, and discharge lines for any blockages, leaks, or damage. Ensure the discharge line is free of kinks.
  • Quarterly Cleaning:
    1. Disconnect power to the pump and the HVAC unit.
    2. Use the lift-to-test tab to drain the tank, or manually remove any remaining water.
    3. Carefully remove the pump cover.
    4. Clean the collection tank, floats, and impeller area to remove any sludge, debris, or mineral deposits. A mild detergent and soft brush can be used.
    5. Spoel alle ûnderdielen goed ôf mei skjin wetter.
    6. Reassemble the pump, ensuring the cover is securely in place.
    7. Reconnect power and test the pump using the lift-to-test tab.
  • Untladingsline: Periodically check the discharge line for algae or mineral buildup, especially if the pump is handling acidic condensate. Clean or replace the tubing as necessary.

7. Probleemoplossing

ProbleemMooglike oarsaakOplossing
De pomp draait netGjin macht oan 'e pompCheck power cord connection, circuit breaker, and GFCI.
Float switch stuck or obstructedDisconnect power, remove cover, clean floats and tank.
Pomp rint mar lit gjin wetter útDischarge line clogged or kinkedInspect and clear the discharge line. Ensure no kinks.
Check valve obstructedDisconnect power, remove and clean the check valve.
Impeller ferstoppeDisconnect power, remove cover, clean impeller area.
Pomp rint kontinuFloat switch stuck in "on" positionDisconnect power, remove cover, clean floats and tank.
Leak in discharge line or check valveInspect all connections and the discharge line for leaks. Tighten or replace as needed.
De pomp is lawaaierichDebris in impeller or motorDisconnect power, remove cover, clean impeller area.
Pump not levelAdjust pump placement using the bullseye level.

8. Spesifikaasjes

  • Model: BK171UL
  • Voltage: 115V
  • Maximum Lift: 17 ft
  • Flow Rate: 112 GPH @ 1 ft lift
  • Ampleeftiid: 1.1 Amps
  • Wattage: 60 watt
  • Frekwinsje: 60 Hz
  • Opfangtankkapasiteit: 2.5 Quarts
  • Ferbining fan ûntslach: 3/8" O.D. barbed check valve
  • Ynlaatferbiningen: Four 1-1/8" diameter holes
  • Stromkabel: 6 ft grounded with plug
  • Maximum Condensate Water Temperature: 150°F
  • Materiaal: Acrylonitril Butadien Styrene (ABS), Plastic
  • Ofmjittings (L x B x H): 11.2" x 5.2" x 6.6"
  • Item Gewicht: 3.7 pûn sterling
  • Feiligensfunksjes: Integrated safety switch, Thermally protected motor
  • Sertifikaasjes: UL/cUL listed in U.S./Canada
Beckett BK171UL Condensate Pump dimensions

Image 8.1: Dimensions of the Beckett BK171UL Condensate Pump.

9. Garânsje en stipe

The Beckett BK171UL Condensate Pump comes with a 3-jierrige fabrikant garânsje. For warranty claims, technical assistance, or replacement parts, please contact Beckett Corporation customer support. Keep your purchase receipt as proof of purchase.

For further assistance, please refer to the official Beckett Corporation website of nim kontakt op mei harren klanteservice ôfdieling.

© 2023 Beckett Corporation. All rights reserved.